Technical data
www.dimplex.de/en
56
2010
Heat pump regulation and accessories
Heating controller – heat pump manager
WPM 2006 plus
WPM EconPlus
Controller for the heat pump heating system for installation in frost-free rooms, with large back-lit LC display, time-controlled lowering
and raising of the heating characteristic curves, time functions for DHW preparation according to need using the heat pump, with optio-
nal targeted reheating via flange heater. „Bivalent-renewable“ operating mode for combining the heat pump with additional renewable
energy sources such as wood or solar energy; dynamic input menus with different levels for technicians and users. Two independent mi-
xer outputs for controlling an additional heat generator and a maximum of two mixed heating circuits. Automatic program for targeted
heat drying of screed floors. PC, modem and bus connection via plug-in modules (special accessories); external sensor (standard NTC-2)
included in the scope of supply.
Order reference Art.-Nr. Features Width x Height x
Depth
mm
Weight
kg
WPM 2006 plus 352550
Delivered as a wall mounted controller in the scope of supply of
the air-to-water heat pump for outdoor installation.
370 x 330 x 90 4.1
WPM EconPlus 355950
Delivered as a wall mounted controller in the scope of supply of
the air-to-water heat pump for outdoor installation. Integrated
thermal energy meter with separate evaluation for heating and
domestic hot water preparation. Simplified electrical connection
with separate terminal blocks for 24 V and 230 V.
303 x 489 x 120 5.0
WPM 2006 plus 352550 4015627352551
WPM EconPlus 355950 4015627355958
Heat pump manager extension module
NWPM
EWPM
The NWPM extension module acts as an interface between the heat pump manager and an Ethernet network. This extension allows the
remote setting and remote monitoring of the heat pump. A PC with a network card or a home network is required for this. The module
can record and save data. This extension is independent of the operating system.A data exchange with a KNX/EIB bus system, and thus
the connection of the heat pump manager to a building management technology system is provided via the EWPM extension module.
This extension makes it possible to set and monitor the heat pump via an installation bus.
Order reference Art.-Nr. for device type Features
NWPM 356960
WPM 2004 / 2006 / 2007
WPM EconPlus
Heat pump manager extension module for
connection to an Ethernet network.
EWPM 356970
WPM 2006 / 2007
WPM EconPlus
Heat pump manager extension module for
connection to the KNX/EIB bus.
LWPM 410 339410
Extension module (RS485) for the heat pump
manager for data transfer via Modbus interface
protocol.
Extension modules can be used from software version H_H50 onwards!
NWPM 356960 4015627356962
EWPM 356970 4015627356979
LWPM 410 339410 4015627339415
Thermal energy meter for connection to the heat pump manager
WMZ ..
Thermal energy meter, consisting of a hydraulic assembly for flow and return flow (heating circuit) and electronic flow rate and
temperature detection. Low pressure loss thanks to flow measurement via Kármán vortex street in the flow and integrated temperature
sensor in the return flow (immersion sleeve). Electronics module for connection to the heat pump manager with separate evaluation for
preparation of heating water, domestic hot water (exception: compact heat pumps) and swimming pool water.Transitional screw con-
nections for direct connection of the WMZ 25 to the KPV 25 / DDV 25 or of the WMZ 32 to the DDV 32 included in the scope of supply.
Order reference Art.-Nr. Nominal width Features Weight
kg
WMZ 25 358220
25 For volume flows of 0.5 – 2.5 m
3
/h 2.1
WMZ 32 358810
32 For volume flows of 1.0 – 5.0 m
3
/h 3.0
To evaluate the measured data, the heat pump manager requires software version H_6x (software update required). High-efficiency air-to-water
heat pumps have thermal energy metering already integrated. Note: The thermal energy meter complies with the quality requirements of the
BAFA (= German Federal Office of Economics and Export Control) market incentive programme subsidizing efficient heat pumps. The thermal
energy meter is not subject to obligatory calibration, and can thus not be used for the heating cost billing procedure!
WMZ 25 358220 4015627358225
WMZ 32 358810 4015627358812
Accessories for heat pump for heating purposes