Technical data

www.dimplex.de/en
44
2010
Max. flow temperature for heating 58 °C
Flow temperature cooling min. 7 °C
Casing colour white
Reversible brine-to-water heat pump
Optimised for heating and cooling with waste heat reco-
SI 130TUR+
Heat pump for heating and cooling with integrated regulation installed indoors. Variable connection options for brine and heating con-
nections on the rear wall of the casing. Access for servicing from the front, no minimum clearance required on the sides, accessible from
underneath with a lift truck. A sound-optimised insulated metal casing and integrated solid-borne sound insulation with free-swinging
compressor base plate, make direct connection with the heating system possible. High coefficients of performance due to compliance
with EN 14511 for larger volume flows on the heat consumption side. Optimised heating and cooling operation via an external four-way
reversing valve which is activated by the controller (special accessory). Reversible refrigerating circuit with additional heat exchanger
for higher DHW temperatures in heating operation and waste heat recovery in cooling operation. Sensor monitoring of the refrigerating
circuit for high degree of operational safety; integrated thermal energy metering (display of the calculated thermal energy volume for
heating and domestic hot water preparation on the WPM EconPlus heat pump manager). The control panel is integrated into a brown-
red design screen and can also be used as wired remote control using the wall mounting set (special accessories MS PGD). Universal
design with the option of flexible expansion for:
Bivalent or bivalent-renewable operating mode
combined distribution systems for heating and cooling
unmixed and mixed heating and cooling circuits
Combination of active and passive cooling (special accessory)
Silent cooling via panel heating/cooling systems requires the use of the room climate control station (special accessory) to regulate the
flow temperature on the basis of the air temperature and humidity of a reference room. Soft starter, load contactor for brine circulating
pump, integrated flow and return flow sensor; external sensor (standard NTC-2) and dirt filter for brine circuit included in the scope of
supply.
Lower operating limit heat source (heating operation) -5 °C ; Upper operating limit heat source (heating operation) 25 °C ;
Lower operating limit heat source (cooling operation) 10 °C ; Upper operating limit heat source (cooling operation) 30 °C ;
Refrigerant R410A ; Connection voltage 3/N/PE ~400 V, 50 Hz
Order reference Art.-Nr. Heat output with
1 compressor /
COP B0/W35
Heat output with
2 compressors /
COP B0/W35
Cooling capacity
with 2 compressors /
EER B20/W9
Width x Height x
Depth
mm
Weight
kg
SI 130TUR+ 361770
57.6 / 4.5 (4.4) 108.5 / 4.3 (4.2) 129.0 / 5.6 1350 x 1890 x 775 830
Heat output and COP according to EN255 (EN 14511) at B0/W35 (B0 = brine inlet temperature 0 °C, W35 = heating water outlet temperature +35 °C).
Cooling capacity and coefficient of performance according to EN 14511.
If borehole heat exchangers which use water as their heat transfer medium are used, a water-to-water heat pump must be installed!
The SI 130TUR+ is also a
vailable upon request in a WI 140TUR+ version, which works with water as the heat source.
The performance values stated can only be achieved in combination with the external four-way valve available as an accessory!
Delivery time on request!
SI 130TUR+ 361770 4015627361775
Four-way reversing valve, reversible brine to water heat pump
Special hydraulic accessories for cooling
VWU 65
The four-way reversing valve (DN 65 flange or DN 80 flange) for integration into the heating flow allows optimised heating and cooling
operation of the SI 130TUR+ reversible brine-to-water heat pump. Switching takes place via a pre-assembled electromotive actuator
(1/N/PE ~230 V) which is activated by the WPM EconR heat pump manager.
Order reference Art.-Nr. for device type Maximum volume
flow
m³/h
Features Weight
kg
VWU 65 362760
SI 130TUR+
2 0
Four-way reversing valve for switching from
heating to cooling operation in flow and/or
return. Actuator, 3-point control signal, 1/N/
PE ~230 V, 50 Hz for short switching times.
15
VWU 80 362770
25 23
VWU 65 362760 4015627362765
VWU 80 362770 4015627362772
Flow switch for rev. SI 130TUR+ brine-to-water heat pump
DFS 80
DN 80 external thread/external thread pipe assembly with flow switch (switch point at 6.5 m
3
/h ±10 %) for SI 130TUR+ brine-to-water
heat pumps. Can be used for flow rate monitoring in the heating circuit and in the brine circuit.
Order reference Art.-Nr. for device type Connection heating
Weight
kg
DFS 80 361840
SI 130TUR+ 3 3
DFS 80 361840 4015627361843
Heating and cooling – ground / ground water as heat source