Technical data
www.dimplex.de/en
42
2010
Heating and cooling – ground / ground water as heat source
Passive cooling with brine-to-water or water-to-water heat pump
Passive cooling station with cooling controller
PKS ..
Module for passive cooling via borehole heat exchangers.Consisting of heat exchanger, brine circulating pump, temperature sensor,
passive cooling controller; 3-way distribution valve with electrothermal actuator included in the scope of supply.Cooling operation
mode is added to the existing heat pump manager by an electronic connection between the heating controller and the cooling con-
troller (where the software versions of the heating controller and the cooling controller differ, a software update is necessary and must
be bought from after-sales service).The components are permanently mounted in a white sheet metal casing, which can be mounted
vertically or horizontally.
Order reference Art.-Nr. for device type Cooling
capacity
kW
Features Width x Height x
Depth
mm
Weight
kg
PKS 14 342460
SI(H)
SIK(H)
14 Change-over valve: DN 25
650 x 400 x 320
30
PKS 25 342470
25 Change-over valve: DN 40 32
PKS 14 Econ 362930
HPK 7 – 11TEW
SI 22TU
SI 30 – 75TER+
14 Change-over valve: DN 25 30
PKS 25 Econ 362940
25 Change-over valve: DN 40 32
Transferrable cooling capacity at a brine inlet temperature of approx. 10 °C and a cooling water inlet temperature of 20 °C!
Start-up should be carried out by authorised after-sales service personnel, especially for heating and cooling equipment!
PKS 14 342460 4015627342460
PKS 25 342470 4015627342477
PKS 14 Econ 362930 4015627362932
PKS 25 Econ 362940 4015627362949
Passive cooling controller
WPM PK
WPM Econ PK
Wall-mounted cooling controller with temperature sensors to record the flow and return temperatures. The passive cooling controller
adds cooling operation mode to the existing heat pump manager (where the software versions of the heating controller and the cooling
controller differ, a software update is necessary (subject to a charge)). Both controllers are operated within the network and control a
combined system for heating and passive cooling with brine-to-water or water-to-water heat pumps. The cooling capacity is transferred
via a heat exchanger not included in the scope of supply. This heat exchanger must be configured according to the cooling capacity to
be transferred, the volume flow and the water quality.
Order reference Art.-Nr. for device type Width x Height x Depth
mm
Weight
kg
WPM PK 348190
SI 5 – 130TE
WI 9 – 27TE
370 x 340 x 90 4
WPM Econ PK 360000
SI 30 – 75TER+
SI 130TUR+
WI 50 – 100TU
Start-up (subject to charge) by the after-sales service is required!
WPM PK 348190 4015627348196
WPM Econ PK 360000 4015627360006
Plate heat exchanger, copper-soldered
WTU ...
Copper-soldered stainless steel plate heat exchanger. Max. operating pressure 25 bar, max. operating temperature 185 °C. As an inter-
mediate heat exchanger for passive cooling. Connection for the cold and warm side with 2½“ external thread.
Order reference Art.-Nr. Volume flow
primary
m³/h
Volume flow
secondary
m³/h
Cooling
capacity
kW
Heat source
connection
⬙
Width x Height x
Depth
mm
Weight
kg
WTU 50 362370
16.1 14.3 50
2½
238 x 611 x 145 40
WTU 75 362380
24.1 21.4 75 238 x 611 x 201 63
WTU 100 362390
32.2 28.6 100 238 x 611 x 257 80
WTU 130 362400
41.9 37.1 130 238 x 611 x 341 110
Delivery time on request! Transferrable cooling capacity at a brine inlet temperature of approx. 10 °C and a cooling water inlet temperature of 20 °C!
The general water quality requirements according to the project planning manual for copper-soldered stainless steel plate heat exchangers apply.
WTU 50 362370 4015627362376
WTU 75 362380 4015627362383
WTU 100 362390 4015627362390
WTU 130 362400 4015627362406
Hydraulic passive cooling accessories
DWU ..
ZWU ..
ETS DWU
Order reference Art.-Nr. Pressure drop Dimensions Features Weight
kg
DWU 25 347760
14000 Pa at 2,5m³/h DN 25
Change-over valve for switching the heat
return flow in passive cooling operation.
Essential accessories: Actuator ETS DWU.
1.2
DWU 40 347770
14000 Pa at 3,5 m³/h DN 40 2.1
ZWU 25 348940
14000 Pa at 1,3 m³/h DN 25
Two-way valve for blocking heat flow in pas-
sive cooling operation. Parallel cooling ope-
ration and DHW preparation is possible due
to hydraulic separation of the cooling circuit.
Essential accessories: Actuator ETS DWU.
0.7
ZWU 32 348950
14000 Pa at 1,5 m³/h DN 32 1.1
ETS DWU 347780
Electrothermal actuator for two-way valve
and change-over valve. ~230V, 50 Hz, de-
energised in heating operation, switching
time approx. 3.5 min.
0.2
DWU 25 347760 4015627347762
DWU 40 347770 4015627347779
ZWU 25 348940 4015627348943
ZWU 32 348950 4015627348950
ETS DWU 347780 4015627347786