Technical data

www.dimplex.de/en
20
2010
Heat pump for heating – air source – indoor installation
Max. flow temperature for heating 58 °C
Casing colour white
Low-temperature air-to-water heat pump
Universal design
LI 9TE
Heat pump for indoor installation with integrated regulation WPM 2007 plus. The control panel is integrated into a brown-red design
screen and can also be used as wired remote control using the wall mounting set (special accessories MS PGD). The integrated air flow
with 90° air deflection enables direct corner installation without air ducts or wall installation with air ducts on the air outlet side. Sound-
optimised through low-noise axial-flow fan and vibration-isolated compressor. High coefficients of performance using an evaporator
optimised for heating operation and energy-efficient defrosting by reverse circulation. Universal design with optional DHW preparation
and the option of flexible expansion for:
Bivalent or bivalent-renewable operating mode
Distribution systems with unmixed and mixed heating circuits
Built-in pipe heater (2 / 4 / 6 kW),
Integrated soft starter, flow and return-flow sensors; external sensor (standard NTC-2) included in the scope of supply.
Lower operating limit heat source (heating operation) -25 °C ; Upper operating limit heat source (heating operation) 35 ° C ;
Refrigerant R404A ; Connection heating 1 ; Connection voltage 3/N/PE ~400 V, 50 Hz
Order reference Art.-Nr. Heat output with 1 compressor /
COP A2/W35
Air outlet Width x Height x
Depth
mm
Weight
kg
LI 9TE 352610
7.5 / 3.3 (3.2)
right
750 x 1250 x 680 177
LI 9TEL 352620
left
Heat output and COP according to EN 255 (EN 14511) at A2/W35 (A2 = air intake temperature +2 °C, W35 = heating water outlet temperature +35 °C) .
Delivery times for heat pumps with air output on the left on request!
LI 9TE 352610 4015627352612
LI 9TEL 352620 4015627352629
Max. flow temperature for heating 65 °C
Casing colour white
Medium-temperature air-to-water heat pump
Compact design
LIKI 14TE
Heat pump for indoor installation with integrated regulation WPM 2007 plus. The control panel is integrated into a brown-red design
screen and can also be used as wired remote control using the wall mounting set (special accessories MS PGD). The integrated air flow
with 90° air deflection enables direct corner installation without air ducts or wall installation with air ducts on the air outlet side. High
coefficients of performance thanks to compliance with EN 14511 for larger volume flows on the heat consumption side, optimised high-
performance evaporator for heating operation and dual differential pressureless manifold for reducing pump operating times. Sound-
optimised through low-noise ventilator and insulated metal casing; integrated solid-borne sound insulation for direct connection to the
heating system with free-swinging compressor base plate.
Compact design with optional domestic hot water preparation and integrated components for direct connection of an unmixed heating
circuit (must not be used for bivalent systems):
Heat circulating pump (note the free compression)
Expansion vessel (24 l)
120 l buffer tank (can be dismantled) with integrated switchable supplementary heating 3/6 kW, safety module. Integrated soft starter,
flow and return-flow sensors; external sensor (standard NTC-2) included in the scope of supply. A heat circulating pump not included in
the scope of supply is required for the distribution system.
Lower operating limit heat source (heating operation) -25 °C ; Upper operating limit heat source (heating operation) 35 ° C ;
Refrigerant R417A ; Connection heating ; Connection voltage 3/N/PE ~400 V, 50 Hz
Order reference Art.-Nr. Heat output with 1 compressor /
COP A2/W35
Air outlet Width x Height x
Depth
mm
Weight
kg
LIKI 14TE 356010
10.1 / 3.6 (3.4) right 960 x 2100 x 780 365
Heat output and COP according to EN 255 (EN 14511) at A2/W35 (A2 = air intake temperature +2 °C, W35 = heating water outlet temperature +35 °C) .
For the air circuit, varying duct dimensions are to be used (air intake side 800, air outlet side 600)! Transport heights when disassembled:
Heat pump with hydraulics approx. 1. 65 m, buffer tank approx. 55 cm.
LIKI 14TE 356010 4015627356016
Air connection plate for air outlet side LIKI 14TE
for modification of the air circuit
ABL 14
Air connection plate for mounting on the LIKI 14TE air-to-water heat pump. By mounting the side covering panel onto the left side
of the heat pump, the air outlet side can be moved from the standard right-side air circuit to the opposing left side; side wall painted
(white, similar to RAL 9003) assembly material included.
Order reference Art.-Nr. for device type Weight
kg
ABL 14 358210
LIKI 14 3.5
ABL 14 358210 4015627358218