Technical data
www.dimplex.de/en
19
2010
Heat pump for heating – air source – indoor installation
Air-to-water heat pump with 90° air deflection
Max. flow temperature for heating 58 °C
Casing colour white
Low-temperature air-to-water heat pump
Compact design
LIK 8TE
Heat pump for indoor installation with integrated regulation WPM 2007 plus. The control panel is integrated into a brown-red design
screen and can also be used as wired remote control using the wall mounting set (special accessories MS PGD). The integrated air flow
with 90° air deflection enables direct corner installation without air ducts or wall installation with air ducts on the air outlet side. Sound-
optimised through low-noise axial-flow fan and vibration-isolated compressor. High coefficients of performance using an evaporator op-
timised for heating operation and energy-efficient defrosting by reverse circulation. Compact design with optional domestic hot water
preparation and integrated components for direct connection of an unmixed heating circuit (must not be used for bivalent systems):
• Expansion vessel (24 l)
• Heat circulating pump (free compression 45,000 Pa)
• Overflow valve and safety module
• Buffer tank (50 l) with integrated 2 kW heating element
Integrated soft starter, flow and return-flow sensors; external sensor (standard NTC-2) and 3 flexible connecting hoses (1“, 500mm)
included in the scope of supply.
Lower operating limit heat source (heating operation) -25 °C ; Upper operating limit heat source (heating operation) 35 ° C ;
Refrigerant R404A ; Connection heating 1 ⬙
Order reference Art.-Nr. Heat output with
1 compressor /
COP A2/W35
Connection voltage Air outlet Width x Height x
Depth
mm
Weight
kg
LIK 8ME 352750
7.5 / 3.3 (3.2)
1/N/PE ~230 V, 50 Hz
right 750 x 1900 x 680 245
LIK 8TE 352590
3/PE ~400 V, 50 Hz
LIK 8TEL 352600
left 750 x 1900 x 650 264
Heat output and COP according to EN 255 (EN 14511) at A2/W35 (A2 = air intake temperature +2 °C, W35 = heating water outlet temperature +35 °C) .
Delivery times for heat pumps with air output on the left on request!
LIK 8ME 352750 4015627352759
LIK 8TE 352590 4015627352599
LIK 8TEL 352600 4015627352605
Max. flow temperature for heating 58 °C
Flow temperature cooling min. 7 °C
Casing colour white
Reversible air-to-water heat pump
Compact design optimised for heating
LIK 8MER
Heat pump for heating and cooling for indoor installation with integrated WPM 2007 R controller. The control panel is integrated into a
brown-red design screen and can also be used as wired remote control using the wall mounting set (special accessories MS PGD). The
integrated air flow with 90° air deflection enables direct corner installation without air ducts or wall installation with air ducts on the
air outlet side. Sound-optimised through low-noise axial-flow fan and vibration-isolated compressor. High coefficients of performance
using an evaporator optimised for heating operation and energy-efficient defrosting by reverse circulation. Must not be used for bivalent
systems. Compact design with optional DHW preparation and integrated components for direct connection with fan convectors:
• Expansion vessel (24 l)
• Heat circulating pump (free compression 45,000 Pa)
• Overflow valve and safety module
• Buffer tank (50 l) with integrated 2 kW heating element
Integrated soft starter, flow and return-flow sensors; external sensor (standard NTC-2) and 3 flexible connecting hoses (1“, 500mm)
included in the scope of supply.
Lower operating limit heat source (heating operation) -25 °C ; Upper operating limit heat source (heating operation) 35 °C ;
Lower operating limit heat source (cooling operation) 15 °C ; Upper operating limit heat source (cooling operation) 40 °C ;
Refrigerant R404A ; Connection heating 1 ⬙ ; Connection voltage 1/N/PE ~230 V, 50 Hz
Order reference Art.-Nr. Heat output with
1 compressor /
COP A2/W35
Cooling capacity
1 compressor /
EER A27/W7
Connection heating
⬙
Width x Height x
Depth
mm
Weight
kg
LIK 8MER 352790
7.5 / 3.3 (3.2) 7.9 / 2.6 1 750 x 1900 x 680 250
Heat output and COP according to EN 255 (EN 14511) at A2/W35 (A2 = air intake temperature +2 °C, W35 = heating water outlet temperature +35 °C).
Cooling capacity and coefficient of performance according to EN 14511.
Start-up should be carried out by authorised after-sales service personnel, especially for heating and cooling equipment!
LIK 8MER 352790 4015627352797