Technical data

Control and Regulation 7.1.2
www.dimplex.de 47
7 Control and Regulation
The elements of the simplified regulation of air-to-water heat
pumps and brine-to-water heat pumps are identical. The controls
are integrated in the unit with the brine-to-water heat pumps
installed. By contrast, the air-to-water heat pumps installed
outdoors are equipped with a remote controller which is normally
installed inside the building. With the air-to-water heat pump LAK
10MR, the room temperature recording and regulation is
integrated in the remote controller and must therefore be placed
in the respective reference room.
The controller board is integrated in the housing of both device
types and the respective cover of the heat pump must be
dismantled for this purpose. The regulation elements and
displays of the two heat pump type differ as described below:
7.1 Regulation and display with air-to-water heat pumps
7.1.1 Remote controller for return temperature regulation
The air-to-water heat pumps installed outdoors are equipped
with a remote controller as shown in figure 7.1. This remote
controller is mounted inside the building and controls all functions
of the heat pump. The heat pump can be switched on with switch
1 or set to "standby" operation. The heat pump is supplied with
line voltage in "standby" operation to keep the antifreeze function
active. If the heating water temperatures drop below 10 °C in
heating mode, the heat circulating pump is first started and if this
does not lead to an increase of the heating water temperature,
the compressor is also activated.
Switch 3 of the remote controller is used to switch between the
two operating modes "Heating" and "Cooling". The heat pump
responds to a change of the operating mode with a delay of
approx. 10 min. to prevent direct switching from heating to
cooling operation.
The return set temperature of the heating water can be set with
setpoint regulator 4.
Fig. 7.1: Wall-mounted remote controller of air-to-water heat pumps
1) Switch ON/Standby
2) The green LED lights up independent of the switch position
(indicating the heat pump is ready for operation)
3) "Heating switch" (left-hand position)
"Cooling" switch (right-hand position)
4) Setpoint regulator for heating water temperature
7.1.2 Remote controller with room temperature sensor for room temperature regulation
(only LAK 10MR!)
The remote control with room temperature sensor should be
installed in a reference room at a suitable location (height
approx. 1 m) in the building. Based on experience, a living room,
for example, is a suitable reference room. Based on the
temperature in this room, the entire heating of the building is then
regulated. The heat pump can be switched on and off with the
remote controller whereby switching off means that the heat
pump is set to "standby" operation. If the heat pump is supplied
with line voltage, the antifreeze function of the heat pump
remains active, as already described.
Furthermore, the heating or cooling operating modes as well as
the setpoint of the room temperature can be adjusted with the
remote controller.
Fig. 7.2: Wall-mounted remote controller of air-to-water heat pumps
1) Switch ON/Standby
2) The green LED lights up independent of the switch position
(indicating the heat pump is ready for operation)
3) "Heating switch" (left-hand position)
"Cooling" switch (right-hand position)
4) Setpoint regulator for room temperature

