Technical data

4.2
12
4.2 Reversible Air-to-Water Heat Pumps for Outdoor Installation, Single-
phase
Device information for air-to-water heat pumps for heating purposes
1 Type and order code
LA 6MR LA 8MR LA 10MR
2Design
2.1 Design Reversible Reversible Reversible
2.2 Degree of protection according to EN 60 529
for compact devices and heating components
IP24 IP24 IP24
2.3 Installation location Outdoors Outdoors Outdoors
3 Performance data
3.1 Operating temperature limits:
Heating water flow/return flow °C / °C up to 60 / above 18 up to 60 / above 18 up to 60 / above 18
Cooling, flow
1
°C
1. See operating limits diagram
+7 to +20 +7 to +20 +7 to +20
Air (heating) °C -20 to +35 -20 to +35 -20 to +35
Air (cooling)
1
°C
+15 to +40 +15 to +40 +15 to +40
3.2 Heat output / COP at A7 / W35
2
kW / ---
2. This data indicates the size and capacity of the system. For an analysis of the economic and energy efficiency of the system, other parameters, such as, in particular, defrosting
capacity, bivalence point and regulation, should also be taken into consideration. The specified values have the following meaning, e.g. A7 / W35: external air temperature 7 °C
and heating water flow temperature 35 °C.
6,1 / 3,3 7,4 / 3,3 8,5 / 3,4
at A7 / W45
2
kW / ---
6,1 / 2,7 7,3 / 2,7 8,4 / 2,8
3.3 Cooling capacity / COP at A35 / W18 kW / --- 7,9 / 3,2 9,4 / 3,3 11,1 / 3,3
at A35 / W7 kW / --- 6,4 / 2,7 7,7 / 2,9 9,0 / 2,9
3.4 Sound power level dB(A) 70,0 71,0 71,0
3.5 Sound pressure level at a distance of 10 m (air outlet side) dB(A) 45,0 46,0 46,0
3.6 Heating water flow m³/h 1,1 1,3 1,5
3.7 Free compression of heat circulating pump (max. level) Pa 34800 35600 33800
3.8 Refrigerant; total filling weight type / kg R407C / 1.5 R407C / 2.3 R407C / 2.7
3.9 Max. output of electric heating element (2nd heat generator)kW 6 6 6
4 Dimensions, connections and weight
4.1 Device dimensions H x W x L cm 86 x 127 x 67 86 x 127 x 67 86 x 127 x 67
4.2 Device connections to heating system Inch Thread 1'' external Thread 1'' external Thread 1'' external
4.3 Weight of the transportable unit(s) incl. Packing kg 159 165 170
5 Electrical Connection
5.1 Nominal voltage; fuse protection V / A 230 / 20 230 / 20 230 / 25
5.2 Heat element fuse (230 V devices only) A
30
3
3. The electrical connection for the heating element requires its own mains cable with separate fuse.
30
3
30
3
5.3 Nominal power consumption
2
A2 W35 kW
1,9 2,3 2,5
5.4 Starting current with soft starter A 26 32 38
5.5 Nominal current A2 W35 / cosϕ A / --- 10.3 12.5 13.6
6 Complies with the European safety regulations
4
4. See CE declaration of conformity
44
7 Additional model features
7.1 Defrosting Automatic Automatic Automatic
Type of defrosting Reverse circulation Reverse circulation Reverse circulation
Defrosting tray included Yes (heated) Yes (heated) Yes (heated)
7.2 Heating water in device protected against freezing
Yes
5
5. The heat circulating pump and the heat pump controller must always be ready for operation.
Yes
5
Yes
5
7.3 Performance levels 111