Specifications
Dimplex Thermal Solutions 1800-YOU-KOOL       
GENERAL INFORMATION 
REGARDING DESIGN TEMPERATURE 
Our custom chiller systems are designed to 
maintain the temperature of cooling fluids within a 
selected temperature range. Each of our units is 
tested through monitored operation within design 
parameters. This enables our experienced 
technicians to calibrate all instrumentation 
precisely to the customers needs and verify that 
each individual unit will function as specified. 
Supporting test data is enclosed either in digital 
format or in print. 
The units are designed to operate efficiently within 
given parameters. Due to varying heat exchange 
rates outside of design temperature, it is highly 
recommended that the machine operate only at 
temperatures within 10°F of the specified 
temperature.  Consult the factory if a process 
requires changes in excess of 10°F in either 
direction of design temperature. 
INSTALLATION: 
1.  Read and follow all information included with 
the chiller manual. 
2.  Read and understand all warning labels and 
tags on the chiller before installation. 
3.  Ensure the unit is placed on a flat, level, hard 
surface. Unless the chiller has been built for 
outdoor operation, it must be placed indoors.  
Space above and around the unit must be 
capable of dissipating the heat rejected by the 
chiller and allow room for servicing. Keep the 
unit at least 3ft away from walls or other 
objects and allow full access to all openings 
and electrical enclosures. At a minimum, 8ft of 
clearance is required above the unit for proper 
air circulation around the chiller as shown in 
Fig 1. 
4.  Chillers with solid feet should be secured using 
the provided mounting holes if possible. Units 
that have caster wheels should be locked to 
ensure the chiller does not move around. 
Figure 1. Minimum Installation Clearances 
5.  Connect fluid lines to the proper fittings from 
the process to the chiller marked “FLUID INLET 
TO CHILLER” and “FLUID OUTLET FROM 
CHILLER”. Make sure that the flow of fluid to 
and from the unit can not be shut off or 
blocked while the chiller is in operation. Piping 
size should be large enough to match the fluid 
flow conditions, generally the size of the 
fittings on the chiller. 
6.  Fill the process plumbing and, if applicable, the 
chiller reservoir with the proper type and 
amount of fluid. Check with the 
manufacturer of the process equipment 
for specific fluid requirements. Refer to 
the “Process Fluid Recommendations” 
section of the manual for information on 
using water in the chiller. 
7.  Purge any air out of the fluid system to ensure 
that the pump suction is flooded. If possible, 
bleed any air trapped in the pump by opening 
the vent plug at the top of the pump until no 
more air comes out and fluid is present in the 
pump cavity. 
DO NOT ALLOW THE FLUID PUMP TO RUN DRY. 
THIS WILL DAMAGE THE PUMP SEALS AND 
WILL NOT BE COVERED UNDER WARRANTY. 
8.  Connect any communication wiring between 
the chiller and process equipment including 
remote controls and interlocks. All 
communication and remote wiring is to be 
provided by the customer. Refer to the chiller’s 
electrical prints for information on wiring 
locations. 










