Specifications
Dimplex Thermal Solutions 1800-YOU-KOOL       
Low refrigerant 
pressure fault - 
(Automatically 
reset when 
satisfied with 
pressure) 
  Low ambient air temperature. 
  Loss of fluid flow through 
evaporator. 
  Loss of refrigerant. 
  Refrigerant solenoid not 
functional. 
  Faulty pressure switch. 
  Compressor crankcase not warm 
or faulty crankcase heater. 
  Ensure chiller is operating within its 
designed ambient temperature specification. 
  Check fluid flow and ensure evaporator is 
clean. 
  Have a refrigerant technician leak check unit 
and charge with the appropriate refrigerant. 
  Check wiring to solenoid or replace valve. 
  Replace pressure switch. 
  Ensure main power disconnect has been on 
for at least 8 hours prior to use. Replace 
crankcase heater if faulty. 
High refrigerant 
pressure fault - 
(Manually reset
inside of chiller) 
(Example of a 
high pressure 
switch shown) 
AIR COOLED CHILLERS:
  Air filters dirty. 
  Condenser dirty. 
  Incoming air too hot. 
  Inoperative fans. 
  Back panel out of chiller. 
  Phase rotation incorrect. 
  Refrigerant system overcharged. 
WATER COOLED CHILLERS:
  Low water flow to condenser. 
  Condenser dirty. 
  Regulating valve operating 
incorrectly. 
  Refrigerant system overcharged. 
  Clean filters (See maintenance section). 
  Clean condenser (See maintenance section). 
  Ensure the chiller is properly ventilated with 
fresh air not exceeding 90°F, unless 
designed for high-ambient temperature 
operation. 
  Check for blown fan fuses. 
  Ensure all covers and panels are in chiller. 
  Correct phase rotation at incoming power. 
  Have a refrigeration technician ensure the 
system is properly charged. 
  Check condenser water supply and pressure. 
  Clean condenser. 
  Have a refrigeration technician adjust the 
valve to the proper pressure setting and 
check operation. 
  Have a refrigeration technician ensure the 
system is properly charged. 
Compressor 
overload - 
(May be manually 
or automatically 
reset, depending 
on compressor) 
  Compressor running too hot. 
  Temperature setpoint too high. 
  Refrigerant pressures too high or 
low. 
  Faulty overload module. 
  Low voltage to chiller. 
  Defective compressor. 
  Allow compressor to cool, then restart unit. 
  Move temperature setpoint to +/- 10°F of 
factory setting. 
  Have a refrigeration technician monitor 
pressures and determine cause. 
  If compressor will run, check amp draw on 
compressor leads to verify compressor is ok. 
  Correct incoming voltage. 
Replace compressor. 










