Installation guide
Ascari MA12 -p. 6 -
1.4 - Menu Options
The set-up menu should be configured as follows, some of these parameters will be modified by instructions in
the previous sections.
Option Setting
01  1 mandatory
02  80
o
C or as required 21-80
o
C
03  30
o
C or as required 21
o
C- maximum temperature set
04  1 if operating from a switched live or if a room thermostat
installed 0 if not
05  1 if option 4 set to 1
06  1 recommended (unless instructed otherwise)
07  0 mandatory
11  1 min or user defined 1-6minutes delay in switching
elements.
12  1 if boiler connected to indirect hot water cylinder
 0 if boiler used for heating only.
13  0 mandatory.
15  1 for 12kw boiler operation
for reduced maximum output power see ยง 2.7.1
Notes: In normal operation press the + button to check if the room thermostat is calling for heat once, a 1 indicates a call for heat. Press
the + button a second time and if auto-adaptability has been selected the temperature correction applied will be displayed (Option
06 Auto-adaptability adjusts the temperature of the heating circuit for the most efficient and temperature stable operation. )