5. Are any devices that are not UL or IEC approved connected to the same
breaker as any of the DSSI computer equipment?
If the previous conditions do not exist, then the grounding should be adequate
for DSSI operation. Digital recommends that the ground offset voltage between
any two enclosures be measured. However, this only provides data for that
particular moment in time. Ground offset values may change as additional
devices are connected to the same power source.
If the installation exhibits ground offset voltages between interconnected
enclosures that exceed the allowable limits, use one of the following solutions:
1. Have an electrician correct any deficiencies detected during the power
system survey. This is the recommended solution.
2. Install grounding cables between enclosures. Grounding cables are
available from Digital, and come with the necessary hardware for
installation.
Installing additional grounding cables normally reduces the ground voltage
offset sufficiently to meet the requirements. In severe cases, however,
the cables may not be large enough. This is revealed by the ground
offset voltage measurements. If the additional grounding cables are not
adequate, the source of the ground offset voltage must be traced and either
reduced or eliminated.
2–4 DECarray Site Preparation