Installation guide

2
DECarray Site Preparation
The DECarray cabinet is intended for installation in a Class A computer
room environment. Before installing the DECarray, make sure the following
conditions are met:
The DECarray cabinet requires 3-phase ac power. Each phase draws up to
7.2 amperes in a fully configured array.
Adequate space is provided around the DECarray cabinet for opening the
front and rear doors, for accessing cables, and for adequate airflow.
The installation site floor can safely bear the weight of the DECarray
cabinet. The DECarray cabinet with power controller weighs 180 kilograms
(396 pounds); a fully configured DECarray weighs 454 kilograms (1000
pounds).
The system’s configuration sheet has been correctly filled out and is
up-to-date. Blank system configuration sheets can be found in Appendix E.
An adequate number of DSSI adapter modules are installed in the system
to support all the DSSI devices in the DECarray.
The correct NEMA plug or plugs are available (Figure 2–1).
DECarray Site Preparation 2–1