SF200 Storage Array Site Preparation
The SF200 storage array is intended for installation in a Class A
computer room environment. It must be operated in an environment
that meets the conditions specified in Table 1–1.
Before installing the SF200 storage array, make sure the following
conditions are met:
• The SF200 storage array requires 3-phase ac power. Each phase
draws up to 6 amperes in a fully configured array, and produces 6400
Btu of heat per hour.
• Adequate space is provided around the storage array for opening the
front and rear doors, for accessing cables at the rear of the storage
array, and for adequate airflow.
• The installation site floor can safely bear the weight of the storage
array. (The SF200 storage array with power controller weighs 179.62
kilograms [396 pounds]; a fully configured storage array weighs
442.25 kilograms [975 pounds].)
• The system’s configuration sheet has been correctly filled out and is
up-to-date. Blank system configuration sheets can be found in Figures
2–1 and 2–2.
• An adequate number of KFMSA modules exist in the XMI backplane
of the VAX 6000 series system to support all the disk ISEs in the
SF200 storage array. Refer to the KFMSA Module Installation and
User Manual (EK–KFMSA–IM) for more details.
• The correct NEMA plug or plugs are available (Figure 2–3).