Specifications

12. COMMUNICATION REGISTER MAP:
This Communication map is for LG Plus. All the parameters
declared in the communication map are either float or unsigned
long and follows;
Standard : Modbus RTU protocol (Half Duplex)
Baudrate : 2400 / 4800 / 9600 / 19200
Parity : Even / Odd / No
Stopbit : 1 / 2
Modbus Function : 03 (Read holding register)
1
Watts Total
float
40101
Sl.No.
Parameter
Data type
Address
2
Watts R phase
float
40103
3
Watts Y phase
float
40105
4
Watts B phase
float
40107
5
VAR Total
float
40109
6
VAR R phase
float
40111
7
VAR Y phase
float
40113
8
VAR B phase
float
40115
9
PF Ave. (Inst.)
float
40117
10
PF R phase
float
40119
11
PF Y phase
float
40121
23