Specifications

Step
Actions Display Reads
Range/Options/
Comments
9
Press
UP key
Row 1: Decimal
point blinking.
Can be set at
appropriate location
using DOWN key.
Ascertain the
correct scale (Kilo/
Mega/Giga) is
selected. Kilo/
Mega/Giga is placed
on the right hand
side of the display
by Letter K/M/G.
Press UP key to
accept the edited
value.
Row 2 :
Eg: To set 11.00kV
Set first four digits
(1100)as explained
above keep
pressing DOWN
key to place
decimal point at
appropriate location
USE UP/DOWN KEY
Letter K/M/G will
indicate the Kilo/
Mega/Giga.
DANGER :
PT secondary circuits are capable of generating
lethal voltages and currents with their primary circuit energized.
Standard safety precautions should be followed while performing any
installation or service on the device (e.g. removing PT fuses, etc.)
12