Control Strategy Configuration
Overview
Introduction
The UMC800 uses function block diagram configuration architecture to develop control strategies for both
analog and digital control.
A function block can represent a physical input or output, a group of physical inputs or outputs, an internal
calculation, or an internal function such as a PID algorithm.
A single controller configuration can have up to 250 user defined function blocks. Except for the types
listed below, a function block algorithm type can be used any number of times up to the limit of 250
blocks:
PID, On/Off, CARB, and TPSC loops and associated support blocks 8 or 16 maximum
Setpoint Programming and associated support blocks 4 maximum
Setpoint Scheduler and associated support blocks 1 maximum
Selector Switch 4 maximum
Time Proportioning output blocks 16 maximum
Modbus Slave 16 maximum
REFERENCE
Reference material for all Function Blocks can be found in the UMC800 Control Builder
Function Block Reference Guide Document #51-52-25-64.
REFERENCE
Examples of Loop and Logic Control can be found in Appendix A Logic Application
Examples and Appendix B Loop Application Examples.