User`s guide

Control Builder Main Window Menu System
Main Window Menus
Release E UMC800 Control Builder Users Guide 23
1/01
Menu Selection Functionality (The menu selection)
Overview tab
Contains the Overview Display Tag Groups Configuration entry
fields. You can assign signal tags or variables to up to 20 groups
of Overview displays.
Single Point
Panel tab
Contains the Single Point Panel Display Tag Groups
Configuration entry fields. You can assign signal tags and
variables to up to 2 groups of Single Point panel displays.
Multi Point
Panel tab
Displays the Multi Point Panel Groups Configuration entry
fields. You can assign signal tags and variables to up to 4 groups
of Multi Point panel displays.
Tag Order
Displays the Tag Order selection menu. Select from those listed below.
Tag Order Groups
Loops
Displays the Loop Tag Order dialog box. Allows you to arrange
up to 16 Loop Tags that can be selected for display, in various
formats, on the operator interface. The order in which they
appear in this box can be changed to coincide with the order in
which you want them to be displayed.
SP
Programmers
Displays the SPP Display Tag Order dialog box. Allows you to
assign SP Programmer block tags to 8 groups of Setpoint
Program overview displays.
HOA Switches Displays the HOA Switches Display Tag Order dialog box.
Allows you to arrange up to 16 HOA tags that can be selected for
display on the operator interface. The order in which they appear
in this box can be changed to coincide with the order in which
you want them to be displayed.
Device
Controls
Displays the Device Controls Display Tag Order dialog box.
Allows you to arrange up to 16 DC tags that can be selected for
display on the operator interface. The order in which they appear
in this box can be changed to coincide with the order in which
you want them to be displayed.
Start up Display
Displays the Start up Display Configurations dialog box. Allows you to enter Title
Text and Comment Text for your start up display.
Message Display
Displays the Message Display Configuration dialog box. You can assign up to 10
sets of Message displays.
Setpoint Scheduler
Display
Displays the Setpoint Scheduler Display Label Configuration dialog box. Allows
you to assign labels to 8 Main Output labels, 8 Auxiliary Output labels, and 16 Event
output labels.
Display Buttons [18] Displays the Display Buttons Configuration dialog box. You can select a display
format and select a Group, Loop tags or SPP tags for each of 8 Display Buttons.
OI Settings
Displays the Operator Interface Settings dialog box. You can enable/disable
Operator or Engineer security and assign security codes for each.
OI File Names