Appendix E Measuring pH with UMC800 Controller and Durafet II Cap Adapter
Sample Help Displays
Release E UMC800 Control Builder Users Guide 269
1/01
Sample Help Displays
The following are sample displays of what may typically be used in this application.
Develop HELP displays with the following information:
STANDARDIZATION PROCEDURE
1) REMOVE ELECTRODE FROM PROCESS
2) INSERT ZERO BUFFER
3) SELECT PH STANDARDIZE DISP
4) ALLOW PH & TEMP TO STABALIZE
5) USING TEMP VALUE OF BUFFER
ENTER CORRECT BUFFER VALUE AS
BUFFR Z
NEXT PAGE ------------
STANDARDIZATION PROC PG 2
6) WITH STABLE PH, TEMP AND BUFFER
VALUE, SELECT ZERO 7 ENTER
THEN CHOOSE Z CAL TO ZERO
CALIBRATE
7) REMOVE THE ELECTRODE FROM THE BUFFER
AND RINSE WITH DISTILLED WATER
8) PLACE ELECTRODE IN SLOPE BUFFER
9) WAIT FOR STABLE PH AND TEMP
NEXT PAGE ------------
STANDARDIZATION PROC PG 3
10) USING TEMP VALUE, ENTER THE CORRECT
PH IN BUFFRS VALUE
11) WITH STABLE PH AND TEMP, SELECT
SLOPE & ENTER THEN CHOOSE
S CAL TO SLOPE CALIBRATE
12) STANDARDIZATION PROCEDURE IS
NOW COMPLETE
TO INCLUDE STANDARDIZATION SET
INTO UNIT PROGRAM, PROCEED TO
NEXT PAGE