User`s guide
Appendix E – Measuring pH with UMC800 Controller and Durafet II Cap Adapter
Configuration
262 UMC800 Control Builder User’s Guide Release E
1/01
Configuration
Once all electrical connections are made, a very specific function block and display interface configuration
is needed to properly standardize and view the pH measurements. The specific elements of the
configuration for a single measurement are described in Figure 75. Additional measurements would
require duplicating the elements for each sensor to be measured. The copy and paste feature of the Control
Builder software provides a convenient method for this duplication.
Figure 75 Configuring analog inputs and standardize function
pH Input:
Configure the analog input range to ± 500 mV
Configure the high range limit to 500 and the low range limit to –500
Temperature Input:
Configure the analog input range to Pt100, 0 to 100 degC