Release E UMC800 Control Builder User’s Guide 207
1/01
Monitoring Loop Block Types
Introduction
The Loop Block Types are PID, On/Off, TPSC, and Carbon. In addition to changing contained parameters,
controls on the live monitoring dialog box of Loop Control Function Blocks will handle Mode changes
and Accutune initiation.
Mode settings
The radio button groups on the Loop block dialog boxes let you select Setpoint mode and Output mode.
The Mode change will also be reflected in the Live Monitor dialog box under “MODE”. See Figure 63.
Choose the
Mode for use in
the next change
request.
Click on
“Change Mode”.
Current Mode will
show in this field.
Figure 63 Changing modes
Accutune
The PID, TPSC, and Carbon function blocks support Accutune. The On/Off function block does not. You
can initiate Accutune by selecting Accutune from the list of parameters and enabling it and activating the
“Accutune” button on the live monitor dialog box.
The Accutune button will remain depressed and disabled until the controller completes the operation.
To abort Accutune in the UMC800 put the loop in manual mode.