Data Storage Configuration
Data Storage Configuration
200 UMC800 Control Builder User’s Guide Release E
1/01
Alarm/event configuration details
Table 50 lists all the entry fields that appear on the “Alarm/Event’ configuration tab with a description of
the feature when the field is selected.
Table 50 Alarm/event configuration details
Feature Description
Alarm File Name
Enter a File Name. There is a maximum of 8 Alpha Numeric
characters. (DOS File Name restrictions)
Event File Name
Enter a File Name. There is a maximum of 8 characters
Data Type Enable Signal
This enable signal turns storage on and off for Alarm/Events.
From the drop-down menu, select:
NONE – Alarm/Event Storage Enable is started/stopped only through
the operator interface’s Data Storage Control Menu (defaults to Enable
on configuration download), or
ANY DIGITAL TAG – Enable is started/stopped only through the on/off
state of the selected Digital Signal. It will not appear on the operator
interface’s data Storage Control Menu
For detailed information concerning Data Storage Enable, refer to
Overview of Data Storage Enable Conditions (page 187).
Storage Mode
From the drop-down menu, select a storage mode.
Refer to Table 47 for mode definitions.
Batch Enable Signal
This signal starts and stops storage for Alarm/Events configured for
“Batch” storage. It does not affect the “Continuous” storage selection.
From the drop-down menu, select:
NONE – Batch is started/stopped only through the operator interface’s
Data Storage Control Menu (defaults to Stop on configuration
download), or
ANY DIGITAL TAG – Batch is started/stopped only through the on/off
state of the selected Digital Signal. It will not appear on the operator
interface’s Data Storage Control Menu
For detailed information concerning Data Storage Enable, refer to
Overview of Data Storage Enable Conditions (page 187).