User`s guide
Data Storage Configuration
Data Storage Configuration
198 UMC800 Control Builder User’s Guide Release E
1/01
Feature Description
Storage Interval [Refer to Storage intervals (page 185).]
NOTE: For On Command storage mode, there is no storage interval or
start time. (They are not used.)
• Click on “Change”. The “Storage Interval” dialog box will appear.
• Click on the radio button for Minutes, Hours, or Days
and select a storage interval from the Edit box.
Or, click on the radio button for “Once a Month”.
• Click OK.
Start Time [Refer to Storage intervals (page 185).]
NOTE: For On Command storage mode, there is no storage interval or
start time. (They are not used.)
• Click on “Change”. The “Change Time” dialog box will appear.
• In the Edit box in each field, select a start time.
• Click OK.
Batch Enable Signal
This signal starts and stops storage for Point logs configured for
“Batch” storage. It does not affect “Continuous” or “On Command”
storage selections.
From the pull-down menu, select:
NONE – Batch is started/stopped only through the operator interface’s
Data Storage Control Menu (defaults to Stop on configuration
download)
ANY DIGITAL TAG – Batch is started/stopped only through the on/off
state of the selected Digital Signal. It will not appear on the operator
interface’s data Storage Control Menu
For detailed information concerning Data Storage Enable, refer to
Overview of Data Storage Enable Conditions (page 187).
Rollover
Click this box to allow data storage to continue collecting data in a
circular storage mode where the oldest data is discarded as new data
is collected.
Clear this box to allow data storage to stop collecting data when the
file is full. You can configure a Warning Level for Disk Full %.
Warning Level
If you do not select rollover, enter a percent in the appropriate box.