User`s guide

Controller Recipes
Using Recipes to Download Setpoint Profiles
182 UMC800 Control Builder Users Guide Release E
1/01
Using Recipes to Download Setpoint Profiles
Recipes can be given an 8-character name and shown on the Recipe Menu display for user selection
(accessed through the Main Menu selections of the Operator Interface).
A Recipe can also automatically load a stored profile number for use by a specific Set Point Programmer.
To do this connect an Analog Variable to the NPGM pin of the Set Point Programmer block given a name
such as PROFNUM (see figure below). This Variable is added to the variable list for a recipe and given a
number corresponding to the profile number to be loaded. Upon selection and loading of the recipe at the
Operator Interface, the programmer will also load the profile number listed in the recipe. The operation of
the programmer to run this profile is from the standard Set Point Programmer display.
As an example, for a selection of a SP Profile number 2, the entries into the Edit Recipe dialog box would
be: VARIABLE NAME = PROFNUM VALUE = 2
PROFNUM
Up to 50 Analog/Digital
Variables
GAIN-LP2
SP-OUT2
SP-OUT3
SP-OUT4
Recipe Table
Creating a Momentary (One-Shot) Action in a Recipe Download
Figure 50 Initiating a one-shot action