User`s guide
Setpoint Programming
Setup/Edit Setpoint Profile
Release E UMC800 Control Builder User’s Guide 163
1/01
•
Select the segment type you want the segment
selected to be: Soak or Ramp. The default when you
selected a segment number is Ramp.
• Click on radio button to select the segment type.
NOTE: You can configure consecutive ramps or soaks.
When the first segment of a profile is a ramp, the profile
start value will be set to the correct value of PV input #
(ignores starting SP value). To start the profile with the
setpoint value, make the 1
st
segment a soak.
If “Guar. Soak Type”, listed in the properties information
block at the top of the dialog box, is “Per Segment”, you
can select “Guaranteed Soak ON” for the segment.
• Click on the box to turn Guaranteed Soak ON.
NOTE: If “Guar. Soak Type” listed is
• None,
• All Soak, or
• All Segments,
no selection is necessary.
• Enter the value for the ramp or soak selected.
NOTE: The first ramp will always default to the PV
value.
Ramp—The value from which the ramp will start.
Soak—The Soak Segment Setpoint value is the
desired value of the PV during soak segments.
NOTE: The Ramp type and Time units are shown in the
properties information area at the top of the dialog box.
• Enter the value of the Time or Rate for the segment.
Ramp—Time: 0.00 to 999.99 hours or minutes
Rate: 0.00 to 999.99 EU/hour or EU/minute
Soak—Segment soak duration
• Enter the Aux. Out value (if required) for the segment
selected.
Aux. Out is a fixed soak value that is available for
each step of the program.