User`s guide
Setpoint Programming
Setpoint Profile Configuration
158 UMC800 Control Builder User’s Guide Release E
1/01
Properties start/restart tab
On this tab, the information that you will configure relates to:
• entering a restart rate value that will be used in the event of a power loss while a program is running.
It looks like this graphically on the Control Builder. Table 37 describes the parameters and the entry
information for each parameter.
Table 37 Start/restart properties
Parameter Parameter Description Entry Information
Restart Rate
This recovery ramp rate is provided in the event of a
power loss while a program is running. The Restart
Rate value is used to return the process to the last
operating setpoint prior to power loss when restart
input is connected to power off timing block.
Value in Engineering
Units