User`s guide

Setpoint Programming
Setpoint Profile Configuration
Release E UMC800 Control Builder Users Guide 157
1/01
Properties loop/jog tab
On this tab, the information that you will configure relates to:
setting a program or loop with start and end segments,
how many times the Program/loop will be recycled, and
if you require a Jog segment, the segment number to which the program will jump when activated.
It looks like this graphically on the Control Builder. Table 36 describes the parameters and the entry
information for each parameter.
Table 36 Loop/jog properties
Parameter Parameter Description Entry Information
Jog Segment
Logic input (JOG) will cause the profile to jump to the
start of the step designated then continue.
Segment number jog
will go to
Loop
A loop causes a specific set of segments with a start
number and an end number to repeat a specific
number of times.
Start Segment
This designates the number of the first segment of
the loop.
149
End Segment
This designates the number of the last segment of the
loop. The last segment of a program must be a soak
segment. Last segment of a loop can be ramp or
soak.
250
Cycles
This number lets the program repeat (loop) a
specified number of times from beginning to end.
0100
0 = Loop indefinitely
Maximum 100