User`s guide

Setpoint Programming
Setpoint Profile Configuration
156 UMC800 Control Builder Users Guide Release E
1/01
Parameter Parameter Description Entry Information
Guar. Hold Type
Guaranteed Hold will hold the profile value if a PV to
the profile (typically a control loops PV) deviates
specified amounts above or below the profile output.
None
No Guaranteed Hold Click on Radio Button
Per Segment
Lets you select specific segments for guaranteed
soak where you set up the profile ramps and soaks.
Click on Radio Button
All Soaks All soaks will have guaranteed soak.
No selection during program editing.
Click on Radio Button
All Segments All segments will have guaranteed soak.
No selection during program editing.
Click on Radio Button
Guar. Hold Hi
The profile will hold if a PV deviates more than the
value set here above the profile output. During
ramps, the SPP output is also held.
Number in Engineering
Units above the setpoint
outside of which the
timer halts
Guar. Hold Lo
The profile will hold if a PV deviates more than the
value set here below the profile output.
During ramps, the SPP output is also held.
Number in Engineering
Units below the setpoint
outside of which the
timer halts