User`s guide

Setpoint Programming
Setpoint Profile Configuration
Release E UMC800 Control Builder Users Guide 155
1/01
Properties general tab
On this tab, the information that you will configure relates to:
selecting a Ramp type and the assignment of time units to the ramp,
selecting a Guaranteed Hold type and the entry of the high and low Guaranteed hold values.
It looks like this graphically on the Control Builder. Table 35 describes the parameters and the entry
information for each parameter.
Table 35 General properties
Parameter Parameter Description Entry Information
Ramp Type
There are two types of Ramps from which to choose:
Rate
Each ramp segments time specifies the RATE at
which that profiles output will reach the next
segment, where the rate is specified in EU/hour or
EU/minute.
Click on Radio Button
Time
Each ramp segments time is the TIME allotted to the
profiles output to reach the next segments value in
hours or minutes.
Click on Radio Button
Time Units
This selection assigns the time units (hours or
minutes) for all segments.
Hours
For Time ramp type: Time = Hours
For Rate ramp type: Rate = EU/Hour
For Soaks: Time = Hours
0.00 to 999.99
Minutes For Time ramp type: Time = Minutes
For Rate ramp type: Rate = EU/Minutes
For Soaks: Time = Minutes
0.00 to 999.99