User`s guide

Control Strategy Configuration
How to Configure Display Tag Groups
Release E UMC800 Control Builder Users Guide 111
1/01
Single point (rotating) panel displays
Description
Single Point Panel displays provide a single point alphanumeric readout that consists of the tag and current
value. The display sequences through a list of up to 12 analog or digital signals. This selection lets you
configure 2 groups of Single Point (Rotating) Panel Displays. Each group may contain a mix of analog
signal tags, digital signal tags, analog variables, and digital variables.
After you have completed all the group configurations you can select the groups to be displayed and assign
them to a specific operator panel display button. [Refer to O/I Display Buttons (1-8) Configuration (page
126).]
Configuration procedure
Follow the procedure in Figure 23 to configure the Single Point Panel Display Tags Group.
1. Select the Single Point tab
3. Enter the Group Title.
(any mix of numbers letters and spaces)
6.
To ADD a tag,
see Note 1
To INSERT a tag,
see Note 2
Note 1 To Add a signal tag:
Click on ADD. The selected Signal tag or
variable will be placed in the next available
position in the Selected Tags field.
Note 2 To Insert a signal/variable tag:
Select a position in the Selected Tags field, then click on
INSERT. The selected Signal tag or variable will be placed
in the position chosen, and other signal tags will move down
as required. You may only insert to the occupied portion of
the list. An attempt to insert to any empty box will place the
new item in the first empty box.
7. The selected Tag name will be
placed in the Selected Tag field.
2. Select a group from
the pull-down menu
8.Repeat selection for up to 12
tag names for each group
To delete a selected tag name,
click on the position of the tag
name, then click Delete bar.
After all tag names are selected
and positioned, click OK.
4. Select which signals you want
displayed in the Selected Tags field
Select the types of signals to be
displayed from the Pull-down menu.
5.Select a signal in the signal tag list
Figure 23 Single point panel display tag group configuration procedure
See the following example of a Single Point Panel Group Display.