User`s guide
Control Strategy Configuration
How to Configure Display Tag Groups
Release E UMC800 Control Builder User’s Guide 109
1/01
Overview display tag groups
Description
An Overview display will present the current status/state for up to 12 analog or digital tagged points. The
display allows operator entry of values via assigned analog and digital variables. This selection lets you
configure 20 groups of Overview Displays. Each group may contain a mix of analog signal tags, digital
signal tags, analog variables, and digital variables for monitor only and/or operator entries. Analog entries
for variables have range limits and digital variables may be turned on or off (via corresponding label)..
Analog and digital variables listed on overview displays may be adjusted by the user while in operation.
Configure entry limits for analog variables. Use entry limits for analog variables. Use entry limits of 0
(low) and 1 (high) for digital limits.
After you have completed all the group configurations you can select the groups and formats to be
displayed and assign them to a specific operator panel display button. [Refer to O/I Display Buttons (1-8)
Configuration (page 126).]
Configuration procedure
Follow the procedure in Figure 22 to configure the “Overview” Display Tags Group.
1. Select the “Overview” tab
3. Enter the Group Title.
(any mix of numbers letters and spaces)
6.
To ADD a tag,
see Note 1
To INSERT a tag,
see Note 2
Note 1 To Add a signal tag:
Click on ADD. The selected Signal tag or
variable will be placed in the next available
position in the “Selected Tags” field.
Note 2 To Insert a signal/variable tag:
Select a position in the “Selected Tags” field, then click on
INSERT. The selected Signal tag or variable will be placed
in the position chosen, and other signal tags will move down
as required. You may only insert to the occupied portion of
the list. An attempt to insert to any empty box will place the
new item in the first empty box.
7. The selected Tag name will be
placed in the “Selected Tag” field.
Enter min and max display limits
in the appropriate column.
2. Select a group from
the drop-down menu
(20 Groups maximum)
8.Repeat selection for up to 12
tag names for each group
To delete a selected tag name,
click on the position of the tag
name, then click “Delete” bar.
After all tag names are selected
and positioned, click “OK”.
4. Select which signals you want
displayed in the “Selected Tags” field
Select the types of signals to be
displayed from the Pull-down menu.
5.Select a signal in the signal tag list
Figure 22 Overview display tag group configuration procedure
See the following example of an Overview Group Display.