User`s guide

Control Strategy Configuration
How to Configure Display Tag Groups
Release E UMC800 Control Builder Users Guide 105
1/01
Trend group displays
Description
Trend graph displays provide traditional value versus time plots in horizontal or vertical orientation. Up to
six Analog or Digital signal tags can be included on each trend display. This selection lets you configure 4
groups of Trend Displays. Each group may contain a mix of analog signal tags and digital signal tags.
ATTENTION
Displaying Trend Points Logarithmically
If you want trends displayed logarithmically, make sure that the first signal tag selected has
the decimal place setting of 127 (Exponential notation See How to Enter Signal Tags
page 93). The Trend display will then display all the trends logarithmically.
After you have completed all the group configurations you can select the groups and formats to be
displayed and assign them to a specific operator panel display button. [Refer to O/I Display Buttons (1-8)
Configuration (page 126).]
Configuration procedure
Follow the procedure in Figure 20 configure the Trend Display Tags Group.
1
. Select the Trend tab
4
. Select which signals you want
displayed in the Selected Tags list
Select the types of signals to be
displayed from the drop-down menu.
3
. Enter the Group Title.
(any mix of numbers letters and spaces)
6.
To ADD a tag,
see Note 1
To INSERT a tag,
see Note 2
Note 1 To Add a signal tag:
Click on
ADD
. The selected Signal tag or
variable will be placed in the next available
position in the Selected Tags field.
Note 2 To Insert a signal/variable tag:
Select a position in the Selected Tags field, then click on
INSERT. The selected Signal tag or variable will be placed
in the position chosen, and other signal tags will move down
as required. You may only insert to the occupied portion of
the list. An attempt to insert to any empty box will place the
new item in the first empty box.
7
. The selected Signal Tag
will be placed in the
Selected Tag Signal field
2.
Select a group from
the drop-down menu
9. Select a Time Base for
the Trend Display from
the drop-down menu.
10.Repeat
selection for up to 6
tags for each group
To
delete
a selected tag, click on
the position of the tag, then click
Delete bar.
After all tags are selected and
positioned, click
OK
.
5.
Select a signal in the signal tag list
8
. Enter the Scale Low and
Scale High values for each
signal selected.
Figure 20 Trend display tag group configuration procedure
See the following example of a Trend Group Display.