Control Strategy Configuration
How to Configure Display Tag Groups
Release E UMC800 Control Builder Users Guide 101
1/01
Alarm display tag group
Description
The Alarm Display Tag Group configuration tab provides a drop list of Alarm groups. You can configure
10 groups of Alarm Displays. Each group contains a set of selected digital signal tags.
After you have completed all the group configurations you can select the groups to be displayed and assign
them to a specific operator panel display button. [Refer to O/I Display Buttons (1-8) Configuration (page
126).]
For an Overview of Alarms Configuration, refer to Appendix C Alarm Configuration Overview.
Configuration procedure
Follow the procedure in Figure 18 to configure the Alarms Display Tags Group.
1. Select the ALARM tab
2. Select a group from
the drop-down menu.
4. Digital signals will be displayed in
the Selected Tags field
3. Enter the Group Title.
(any mix of numbers letters and spaces)
5.
To ADD a tag,
see Note 1
To INSERT a tag,
see Note 2
Note 1 To Add a signal tag:
Click on ADD. The selected Signal tag will
be placed in the next available position in
the Selected Tags field.
Note 2 To Insert a signal/variable tag:
Select a position in the Selected Tags field, then
click on INSERT. The selected Signal tag will be
placed in the position chosen, and other signal tags will
move down as required. You may only insert to the
occupied portion of the list. An attempt to insert to any
empty box will place the new item in the first empty
box.
6. The selected Signal Tag will be
placed in the Selected Tag field
Repeat selection for up to 12 tags
for each group
To delete a selected tag, click on
the position of the tag, then click
Delete bar.
After all tags are selected and
positioned, click OK.
7.Click to enter detail text
Figure 18 Alarms display tag group configuration procedure
See the following example of an Alarms Group Display.