User`s guide
Control Strategy Configuration
Operator Interface Configuration Overview
Release E UMC800 Control Builder User’s Guide 99
1/01
Operator Interface Configuration Overview
Overview
Modification and customization of the operator interface displays and buttons is done using UMC800
Control Builder software. With the software, data points can be identified (tagged) using eight character
names. Once named, the operator interface using a standard set of display formats and a predefined menu
hierarchy may access these tags.
Selected screens such as bar graphs, trends, and overview displays will require the user to specify the
individual tags to be represented on the screen.
There are several steps in this configuration:
• Selecting which Tags or Groups to display
• Selecting the format and the button for displaying the Tags or Groups
The configurable Operator Interface Display Tag Groups, Displays, Buttons and O/I Security settings are as
follows:
Display Tag Groups Overview
...... Alarm
...... Panel Meter
...... Trend
...... Bar
...... Overview
...... Single Point Panel
...... Multi-Point Panel
Tag Order
...... Loops
...... SP Programmer
...... Hand/Off/Auto
...... Device Control
Startup and Message Displays
Setpoint Scheduler Display
Operator Pushbutton, Selector Switch and Data Entries Configuration
How to Configure Start Up Conditions for Controller Initialization
Display Buttons (1-8)
Making a configuration selection
• The “Configure” menu in the Main window lists the
configurable Display Tag Groups, Displays, and
Buttons.
• Refer to the individual subsections on the following
pages for configuration instructions.
ATTENTION
Pushbuttons F1-F4 groups are configured at the function block level. You can configure up to
four groups (total of 16 pushbuttons) to display on the operator interface. Refer to the Function
Block Reference Guide.