User`s guide

Control Strategy Configuration
How to Configure Function Block Parameters
Release E UMC800 Control Builder Users Guide 97
1/01
Function block inputs
All Function Block Inputs must be connected to a
signal source.
The inputs may be connected to the output of
another function block, to a variable, or a
constant.
Variables are named values that can be
connected to function block inputs and can be
changed from the operator interface.
Variable is a type of drawing item. The variable
holds one value. The value is entered from the
operator interface or a recipe during operation.
The Control Builder cannot set it.
Constants are unnamed objects, external to any
function block that may hold a single value. The
Control Builder sets the value and the operator
interface cannot alter the value.
Constants provide a means to drive unused or
invariant function block inputs.
Inputs
ATTENTION: Variables and constants do not
consume a function block number.
Function block outputs
Function Block Outputs are signals that reflect the
results of a function blocks execution.
A function block may have 0, 1, or more outputs.
An unused output need not be connected.
An output can be connected to any number of
function block inputs including inputs on the same
block.
An output may NOT be connected to another
output, a named variable, or a constant.
Outputs
Function block parameters
All Function Block Parameters are values that
influence the function blocks execution.
Click the cursor on the desired parameter to
highlight it.
Key in the desired value, use the scroll buttons at
the edge of the box or make a selection from the
drop down menu.
Press F1 for help on any active field.
Press OK when configuration is complete to close
the box and save the entries.