Specifications

User Instructions - Digital Positioner 3200MD LGENIM0059-09 12/13
5
Table VII: Hazardous Area Certifi cations
North America (FM/CSA)
Flame Proof
SIRA 03ATEX1387
II 2 GD
Ex d IIB+H2 T5 IP65
Ex tD A21 IP65 T95˚C (Ta =-40°C to +80°C)
T5 (Ta = -40˚C to +80C
Explosion Proof
Class I, Div 1, Groups B,C,D
DIP Class II, III, Div 1 Groups E,F,G
Class I, Zone 1, Ex d IIB+H2 (CSA Only)
T5 Tamb = -40˚C ≤ Ta ≤ +80˚C (CSA Only)
T6 Tamb = -40˚C ≤ Ta ≤ +60˚C
Type 4X
Intrinsically Safe
SIRA 03ATEX2299X
II 1 GD
Ex ia IIC Ex iaD 20 T95˚C
T4 (Ta = -52˚C to +85˚C) (Ta = -52˚C to +80˚C)
T5 (Ta = -52˚C to +55˚C)
Entity Parameters
Ui = 30V
Ii = 100mA
Pi = 800mW
Ci = 30nF Co = 36nF
Li = 0
Intrinsically Safe
Class I,II, III, Div 1, Groups A,B,C,D,E,F,G
Class I, Zone 0, AExia IIC (FM Only)
T4 Tamb = -50˚C ≤ Ta ≤ +85˚C
T5 Tamb = -50˚C ≤ Ta ≤ +55˚C
Type 4X
Entity Parameters
Ui = 30V
Ii = 100mA
Pi = 800mW
Ci = 30nF
Li = 0
Non-Incendive
SIRA 08ATEX4006
II 3 GD
Ex nL nA IIC
Ex tD A22 T95˚C (Ta = -52°C to +80°C)
T4 (Ta = -52˚C to +85˚C)
T5 (Ta = -52˚C to +55˚C)
Non-Incendive
Class I, Div 2, Groups A,B,C,D
T4 Tamb = -50˚C ≤ Ta ≤ +85˚C
T5 Tamb = -50˚C ≤ Ta ≤ +55˚C
Type 4X
Barriers Not Required
IECEx InMetro
Explosion Proof
IECEx SIR 04.0023X
Ex d IIB+H2 T5
Ta = -40˚C to +55˚C
Explosion Proof
TÜV 11.0070
Ex d IIB+H2 T5 Gb IP65
Ta = -40˚C -Ta - +80˚C
Intrinsically Safe
IECEx FMG 05.0003X
Ex ia IIC Ex iaD 20 T95˚C
T4 Ta = -40˚C to +85˚C Ta = -40C to +80˚C
T5 Ta = -40˚C to +55˚C
Entity Parameters
Ui = 30V
Ii = 100mA
Pi = 800mW
Ci = 30nF
Li = 0
Instrinsically Safe
TÜV 11.0071X
Ex ia IIC Ga IP65 Ex ia IIIC T95˚C Da IP65
T4 Ta = -40˚C-Ta- +85˚C Ta = -40˚C-Ta- +85˚C
T5 Ta = -40˚C-Ta- +55˚C
Entity Parameters
Ui = 30Vcc
Ii = 100mA
Pi= 800mW
Ci = 30nF
Li = 0
KOSHA Gost
Explosion Proof
10-AV4BO-0560X
Ex d IIB+H2 T5
T5 Ta = -20°C to +50°C
Special Conditions for Safe Use:
The equipment must be installed in such a manner as to minimize the risk of impact or friction with other metal surfaces.
To avoid possibility of static discharge clean only with a damp Cloth
In order to maintain the explosion proof certifi cations do not remove or loosen covers while circuits are live.
For Intrinsically Safe installations the positioner must be connected to suitably rated intrinsically safe equipment, and must be installed in accordance
with intrinsically safe installation standards.
Substitution of components may impair Intrinsic Safety.