P2.2.4 I/O frequency reference selection 2 ID131
This parameter is used to select different reference input location with digital input
P2.4.2.17 I/O Ref. 2. Selections for this are the same as for the I/O frequency reference
selection 1.
Other parameters related to function
- Digital input P2.4.2.17 I/0 Ref. 1/2
P2.2.5 Speed share ID1241
Defines the speed reference percentage ratio after final reference location but before
shows the reference after speed share
function. Used to adjust reference ration e.g. in line drive that PLC can give same
reference to all drives while speed share compensate gear ratio affect to the line speed.
P2.2.6 Load Share ID1248
Defines the percentage for final torque reference after final torque reference location
selection but before the torque reference step function, torque reference dead zone and
reference filtering.