7.2.1
Basic Parameters
P2.2.1 I/O frequency reference selection 1 ID117
Defines which frequency reference source is used when control place is I/O terminal
P3.1 Control Place
0= AI1 - Analogue Input 1.
S 2.4.2: Input Signals \
1= AI2 - Analogue Input 2.
S 2.4.3: Input Signals \
2= AI1+AI2 - Analogue Input 1 + Analogue Input 2.
With alternative reference scaling in Analogue Input group 100 % input values can be
set to correspond 25 Hz thus when both are at 100 % final reference will be 50 Hz.
3= AI1-AI2
Analogue Input 1 - Analogue Input 2.
4= AI2-AI1
Analogue Input 2 - Analogue Input 1.
5= AI1xAI2
Analogue Input 1 x Analogue Input 2
6= AI1 Joystick
Analogue input 1, -10 Vdc... +10 Vdc
7= AI2 Joystick
Analogue input 2, -10 Vdc... +10 Vdc
8= Keypad
Reference from keypad R3.2
9= Fieldbus
Reference is taken from Fieldbus, alternative scaling can be selected
10= Motor Pot - Motor potentiometer.
Reference handled \
and decrease) \
11= AI1, AI2 min
The minimum of Analogue Input 1 and Analogue Input 2 is used as reference.
12
The maximum from Analogue Input 1 and Analogue Input 2 is used as reference.
13= Max Freq Maximum Frequency
P2.1.2 Max Frequency is used as reference.
14 AI1/AI2 Selection
Input 1 and Analogue
15= Encoder 1
Reference is read from encoder input 1.
16= Encoder 2
Reference is read from encoder input 2. This selection is usable with double encoder
boards. Could be used e.g. for speed synchronization where two motor needs to run
at same speed but not necessarily same angle.