P2.1.7 Motor cos phi ID120
P2.1.8 Motor Nominal Power ID116
Find this value on the rating plate of the motor.
Drive Synch Operation
Motor Nominal power from the motor name plate / Number of drives in parallel using
Vacon Drive Synch.
P2.1.9 Magnetizing current ID612
Set here the motor magnetizing current (no-load current).
Can be measured by running motor without load at 2/3 of nominal speed.
When value is zero the magnetization current is calculated from motor nominal
parameters

    
  
 

    
  
    
 










If given before identification run this is used as reference for U/f tuning when making
identification without rotating the motor.
DriveSynch Operation
Motor Nominal magnetization current / Number of drives in parallel using Vacon Drive
Synch.