User`s manual

70 • Vacon apfiff09 marine
Tel. +358
5
6.13 Fieldbus parameters
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.13.1
Fieldbus min scale
0,00
320,00
Hz
0,00
850
P2.13.2
Fieldbus max scale
0,00
320,00
Hz
0,00
851
P2.13.3
Fieldbus process
data out 1 selection
0
10000
1
852
Choose monitoring data
with parameter ID
Def: Output Frequency
P2.13.4
Fieldbus process
data out 2 selection
0
10000
2
853
Def: Motor Speed
P2.13.5
Fieldbus process
data out 3 selection
0
10000
3
854
Def: Motor Current to FB
P2.13.6
Fieldbus process
data out 4 selection
0
10000
4
855
Def: Motor Torque
P2.13.7
Fieldbus process
data out 5 selection
0
10000
5
856
Def: Motor Power
P2.13.8
Fieldbus process
data out 6 selection
0
10000
6
857
Def: Motor Voltage
P2.13.9
Fieldbus process
data out 7 selection
0
10000
7
858
Def: DC-Link Voltage
P2.13.10
Fieldbus process
data out 8 selection
0
10000
37
859
Def: Last Active Fault
P2.13.11
Fieldbus process
data in 1 selection
0
10000
1140
876
Choose controlled data with
parameter ID.
Def: FB Torque Reference
P2.13.12
Fieldbus process
data in 2 selection
0
10000
46
877
Def: FB Limit Scaling
P2.13.13
Fieldbus process
data in 3 selection
0
10000
47
878
Def: FB Adjust Reference
P2.13.14
Fieldbus process
data in 4 selection
0
10000
48
879
Def: FB Analogue Output.
P2.13.15
Fieldbus process
data in 5 selection
0
10000
0
880
Choose controlled data with
parameter ID
P2.13.16
Fieldbus process
data in 6 selection
0
10000
0
881
Choose controlled data with
parameter ID
P2.13.17
Fieldbus process
data in 7 selection
0
10000
0
882
Choose controlled data with
parameter ID
P2.13.18
Fieldbus process
data in 8 selection
0
10000
0
883
Choose controlled data with
parameter ID
P2.13.19
General Status Word
ID
0
10000
67
897
Choose monitoring data in
General Status Word
P2.13.20
FB Actual Speed
Mode
0
1
0
1741
0=Calculated 1=Actual
P2.13.21
Control Slot Selector
0
8
0
1440
0=All 4=Slot D
5=Slot E
P2.13.22
State Machine
1
2
1
896
1 = Standard
2 = ProfiDrive
P2.13.23
FB Custom Minimum
-32000
+32000
0
898
FB Speed Reference
Minimum scaling
P2.13.24
FB Custom
Maximum
-32000
+32000
+10000
899
FB Speed Rederence
Maximum Scaling
Table 6-36. Fieldbus parameters