Speed error monitoring
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.12.4.1
Speed Error Mode
0
3
0
752
0=No response
1=Warning
2=Fault,stop acc. to 2.3.2
3=Fault,stop by coasting
P2.12.4.2
Speed Error Limit
0,0
100,0
%
5,0
753
P2.12.4.3
Speed Fault Delay
0,00
100,00
S
0,1
754
Table 6-29. Speed error monitoring
6.12.5
Motor thermal protections
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.12.5.1
Thermal protection
of the motor
0
3
2
704
0=No response
1=Warning
2=Fault,stop acc. to 2.3.2
3=Fault,stop by coasting
P2.12.5.2
Motor ambient
temperature factor
100,0
100,0
%
0,0
705
P2.12.5.3
Motor cooling factor
at zero speed
0,0
150,0
%
40,0
706
P2.12.5.4
Motor thermal time
constant
1
200
min
45
707
P2.12.5.5
Motor duty cycle
0
100
%
100
708
P2.12.5.6
Response to
thermistor fault
0
3
2
732
See P2.12.5.1
P2.12.5.7
Over Load Response
0
2
1
1838
0=No response
1=Warning
2=Fault
P2.12.5.8
Over Load Signal
0
2
0
1837
0=Not Used
1=Current
2=Torque
3=Power
P2.12.5.9
Over Load Maximum
Input
0,0
300,0
%
150,0
1839
P2.12.5.9
Over Load
maximum Step
0
10000
200
1840
Table 6-30. Motor thermal protections
6.12.6
Living Zero monitoring
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.12.6.1
Response to 4mA
reference fault
0
5
0
700
0=No response
1=Warning
2=Warning+Previous Freq.
3=Wrng+PresetFreq 2.12.6.2
4=Fault,stop acc. to 2.3.2
5=Fault,stop by coasting
P2.12.6.2
4mA reference fault
frequency
0,00
P2.1.2
Hz
0,00
728