6.12.2
Temperature sensor protections
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.12.2.1
No. of used inputs
on board 1
0
5
0
739
0=Not used (ID Write)
1 = Sensor 1 in use
2 = Sensor 1 & 2 in use
3 = Sensor 1 & 2 & 3 in use
4 = Sensor 2 & 3 in use
5 = Sensor 3 in use
P2.12.2.2
Response to
temperature fault
0
3
2
740
0=No response
1=Warning
2=Fault,stop acc. to 2.3.2
3=Fault,stop by coasting
P2.12.2.3
Board 1 warning
limit
30,0
200,0
120,0
741
P2.12.2.4
Board 1 fault limit
30,0
200,0
130,0
742
P2.12.2.5
No. of uses inputs
on board 2
0
5
0
743
0=Not used (ID Write)
1 = Sensor 1 in use
2 = Sensor 1 & 2 in use
3 = Sensor 1 & 2 & 3 in use
4 = Sensor 2 & 3 in use
5 = Sensor 3 in use
P2.12.2.6
Response to
temperature fault
0
3
2
766
0=No response
1=Warning
2=Fault,stop acc. to 2.3.2
3=Fault,stop by coasting
P2.12.2.7
Board 2 warning
limit
30,0
200,0
120,0
745
P2.12.2.8
Board 2 fault limit
30,0
200,0
130,0
746
P2.12.2.9.1
Channel 1B Warn
-30,0
200,0
0,0
764
P2.12.2.9.2
Channel 1B Fault
-30,0
200,0
0,0
765
P2.12.2.9.3
Channel 1C Warn
-30,0
200,0
0,0
768
P2.12.2.9.4
Channel 1C Fault
-30,0
200,0
0,0
769
P2.12.2.9.5
Channel 2B Warn
-30,0
200,0
0,0
770
P2.12.2.9.6
Channel 2B Fault
-30,0
200,0
0,0
771
P2.12.2.9.7
Channel 2C Warn
-30,0
200,0
0,0
772
P2.12.2.9.8
Channel 2C Fault
-30,0
200,0
0,0
773
Table 6-27. PT-100 protections
6.12.3
Stall Protection
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.12.3.1
Stall protection
0
3
0
709
0=No response
1=Warning
2=Fault,stop acc. to 2.3.2
3=Fault,stop by coasting
P2.12.3.2
Stall current
0,1
2 x I
H
A
I
H
710
P2.12.3.3
Stall time limit
1,00
120,00
s
15,00
711
P2.12.3.4
Stall frequency limit
1,0
P2.1.2
Hz
25,0
712
Table 6-28. Stall protection