User`s manual

apfiff09 marine vacon • 65
24-
5
6.11.1.1
Drive Synch specific parameters
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
2.11.10.1
Drive Synch Follower
fault
0
2
1531
2.11.10.2
Follower phase shift
0,0
360,0
Dec
0,0
1518
2.11.10.3
DC Voltage Blance
Gain
0
1000
100
1519
2.11.10.4
SB Last ID 2nd
0
64
0
1799
Table 6-25. Drive Synch specific parameters
6.12 Protections
6.12.1
Common settings
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.12.1.1
Input phase
supervision
0
3
0
730
0=No response
1=Warning
2=Fault,stop acc. to 2.3.2
3=Fault,stop by coasting
P2.12.1.2
Response to
undervoltage fault
0
1
0
727
0=Fault stored in history
1=Fault not stored
P2.12.1.3
Output phase
supervision
0
3
2
702
See P2.12.1.1
P2.12.1.4
Response to slot
fault
0
3
2
734
See P2.12.1.1
P2.12.1.5
Safe Disable
Response
0
2
1
755
See P2.12.1.1
Table 6-26. Common settings