User`s manual
apfiff09 marine vacon • 51
24-
5
P2.5.6.3
Digital output 1 on
delay
0,00
320,00
s
0,00
487
0,00 = On delay not in use
P2.5.6.4
Digital output 1 off
delay
0,00
320,00
s
0.00
488
0,00 = Off delay not in use
P2.5.6.5
Invert delayed DO1
0
1
0
1587
0=Not inverted
1=Inverted
P2.5.6.6
ID.Bit Free DO
0,00
2000,15
0,00
1217
Table 6-15. Delayed digital output 1 parameters, G2.3.1
6.5.7
Delayed digital output 2
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.5.7.1
Digital output 2
signal selection
0.1
E.10
0.1
489
Possibility to invert by
ID1091 INV Commands
P2.5.7.2
Digital output 2
function
0
28
0
490
See P2.5.6.2
P2.5.7.3
Digital output 2 on
delay
0,00
320,00
s
0,00
491
0,00 = On delay not in use
P2.5.7.4
Digital output 2 off
delay
0,00
320,00
s
0,00
492
0,00 = Off delay not in
use
P2.5.7.5
Invert delayed DO2
0
1
0
1588
0=Not inverted
1=Inverted
P2.5.7.6
ID.Bit Free DO
0,00
2000,15
0,00
1385
Table 6-16. Delayed digital output 2 parameters, G2.3.2
6.5.8
Supervision Limits
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.5.8.1
Output frequency
limit 1 supervision
0
2
0
315
0=No limit
1=Low limit supervision
2=High limit supervision
P2.5.8.2
Output frequency
limit 1;
Supervised value
0,00
320,00
Hz
0,00
316
P2.5.8.3
Output frequency
limit 2 supervision
0
2
0
346
0=No limit
1=Low limit supervision
2=High limit supervision
P2.5.8.4
Output frequency
limit 2;
Supervised value
0,00
320,00
Hz
0,00
347
P2.5.8.5
Torque limit
supervision
0
2
0
348
0=Not used
1=Low limit supervision
2=High limit supervision
P2.5.8.6
Torque limit
supervision value
-300,0
300,0
%
100,0
349
P2.5.8.7
Reducing of torque
supervision limit
0
5
0
402
P2.5.8.8
Reference limit
supervision
0
2
0
350
0=Not used
1=Low limit
2=High limit
P2.5.8.9
Reference limit
supervision value
0,00
100,0
%
0,00
351
P2.5.8.10
FC temperature
supervision
0
2
0
354
0=Not used
1=Low limit
2=High limit
P2.5.8.11
FC temperature
supervised value
10
100
C
40
355
P2.5.8.12
Analogue
supervision signal
0
4
0
356
0=Not used
1=AI1