P2.5.4.7
Analogue output 3
offset
-100,00
100,00
%
0,00
484
Table 6-13. Analogue output 3 parameters, G2.3.7
6.5.5
Analogue output 4
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.5.5.1
Analogue output 4
signal selection
0.1
E.10
0.1
1527
TTF programming
See chapter 3.1 and 3.2
P2.5.5.2
Analogue output 4
function
0
20
5
1520
See P2.5.2.2
P2.5.5.3
Analogue output 4
filter time
0,00
10,00
s
1,00
1521
0=No filtering
P2.5.5.4
Analogue output 4
inversion
0
1
0
1522
0=Not inverted
1=Inverted
P2.5.5.5
Analogue output 4
minimum
0
1
0
1523
0=0 mA (0 %)
1=4 mA (20 %)
P2.5.5.6
Analogue output 4
scale
10
1000
%
100
1525
P2.5.5.7
Analogue output 4
offset
-100,00
100,00
%
0,00
1524
Table 6-14. Analogue output 4 parameters, G2.3.8
6.5.6
Delayed digital output 1
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.5.6.1
Digital output 1
signal selection
0.1
E.10
0.1
486
Posibility to invert by
ID1091 INV Commands
P2.5.6.2
Digital output 1
function
0
28
1
312
0=Not used
1=Ready
2=Run
3=Fault
4=Fault inverted
5=FC overheat warning
6=Ext. fault or warning
7=Ref. fault or warning
8=Warning
9=Reverse
10=Jogging spd selected
11=At speed
12=Mot. regulator active
13=Freq. limit 1 superv.
14=Freq. limit 2 superv.
15=Torque limit superv.
16=Ref. limit supervision
17=External brake control
18=I/O control place act.
19=FC temp. limit superv.
20=Reference inverted
21=Ext. brake control
inverted
22=Therm. fault or warn.
23=On/Off control
24=Fieldbus input data 1
25=Fieldbus input data 2
26=Fieldbus input data 3
27=Warning Set Reset
28=ID.Bit Select