User`s manual

apfiff09 marine vacon • 45
24-
5
P2.4.2.26
Inching 1
0.1
0.1
531
Inching reference 1 (Default
Forward 2 Hz. See P2.4.16). This
will start the drive.
P2.4.2.27
Inching 2
0.1
0.1
532
Inching reference 2 (Default
Reverse -2 Hz. See P2.4.17). This
will start the drive.
P2.4.2.28
Motoring Power limit 1
0.1
0.1
1500
Activates power limit 1
P2.4.2.29
Motoring Power limit 2
0.1
0.1
1501
Activates power limit 2
P2.4.2.30
2
nd
frequency Limit
0.1
0.1
1511
Activates second freq. Limit
P2.2.7.31 2
nd
Freq Limit
P2.4.2.31
Generator Power Limit 1
0.1
0.1
1506
Activates Gen. power limit 1
P2.4.2.32
Generator Power Limit 2
0.1
0.1
1507
Activates Gen. power limit 2
P2.4.2.33
Reset Position
0.1
0.1
1090
P2.4.2.34
MF Mode 2
0.1
0.1
1092
P2.4.2.35
Emergency Stop
0.1
0.2
1213
P2.4.2.36
Motoring Torque Limit 1
0.1
0.1
1624
P2.4.2.37
Generator Torque Limit 1
0.1
0.1
1626
P2.4.2.38
PID Activation
0.1
0.1
1804
P2.4.2.39
Store Parameter Set
0.1
0.1
1753
Stores active parameter set to
selected parameter set
P2.4.2.40
Start Place A/B
0.1
0.1
425
Changes start signals between A
and B places.
P2.4.2.41
Start signal 1B
0.1
A.1
403
Forward, See ID300
P2.4.2.42
Start signal 2B
0.1
A.2
404
Reverse. See ID300
P2.4.2.43
RunRequest Enable
0.1
0.2
1896
Table 6-6. Digital input signals, G2.2.4
6.4.3
Analogue input 1
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.4.3.1
AI1 signal selection
0.1
E.10
A.1
377
Slot . Board input No.
P2.4.3.2
AI1 Reference Filter
TC
0,000
32,000
s
0,000
324
0=No filtering
P2.4.3.3
AI1 signal range
0
3
0
320
0
1
2= -
3= Custom range*
P2.4.3.4
AI1 custom
minimum setting
-160,00
160,00
%
0,00
321
Custom Range:
Minimum input
P2.4.3.5
AI1 custom
maximum setting
-160,00
160,00
%
100,00
322
Custom Range:
Maximum input
P2.4.3.6
AI1 reference
scaling, minimum
value
0,00
320,00
Hz
0,00
303
Selects the frequency
that corresponds to the
min. reference signal
P2.4.3.7
AI1 reference
scaling, maximum
value
0,00
320,00
Hz
0,00
304
Selects the frequency
that corresponds to the
max. reference signal
P2.4.3.8
AI1 joystick Dead
Zone
0,00
20,00
%
0,00
384
Dead Zone for joystick
input
P2.4.3.9
AI1 sleep limit
0,00
100,00
%
0,00
385
Drive goest to stop if
input is below this limit
for this time.
P2.4.3.10
AI1 sleep delay
0,00
320,00
s
0,00
386
P2.4.3.11
AI1 joystick offset
-100,00
100,00
%
0,00
165
Press enter for 1s to set
offset
P2.4.3.12
AI1 filter time
0,000
32,000
s
0,000
1228
Table 6-7. Analogue input 1 parameters, G2.2.2
*Remember to place jumpers of block X2 accordingly.
See NX User's Manual, chapter 6.2.2.2