24-
5
6.3 Ramp Control
6.3.1
Basic Settings
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.3.1
Start function
0
1
0
505
0=Ramp
1=Flying start
P2.3.2
Stop function
0
1
0
506
0=Coasting
1=Ramp
P2.3.3
Acceleration time 1
0,2
3270,0
s
3,0
103
0 Hz to Max frequency
P2.3.4
Deceleration time 1
0,2
3270,0
s
3,0
104
Max frequency to 0 Hz
P2.3.5
Ramp 1 shape
0
100
%
2
500
0=Linear
>0=S-curve ramp time
P2.3.6
Acceleration time 2
0,2
3270,0
s
10,0
502
P2.3.7
Deceleration time 2
0,2
3270,0
s
10,0
503
P2.3.8
Ramp 2 shape
0
100
%
4
501
0=Linear
>0=S-curve ramp time
P2.3.9
Inching Ramp
0,01
320,00
s
1,00
1257
P2.3.10
Reducing of acc./dec.
times
0
5
0
401
Scales active ramp from
100 % to 10 %.
0=Not used
1=AI1
2=AI2
3=AI3
4=AI4
5=Fieldbus
6.3.2
Quick Stop
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.3.11.1
IO Quick Stop Mode
0
1
0
1276
0=Coasting
1= Ramp
P2.3.11.2
Quick Stop Ramp
time
0,1
3200,0
s
1256
6.3.3
Ramp Control Options
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.3.12.1
Ramp: Skip S2
0
1
0
1900
P2.3.12.2
CL Ramp
Follower Encoder
Frequency
0
1
0
1902
P2.3.12.3
Ramp Input
Interpolator TC
0
200
ms
10
1184