User`s manual

42 • Vacon apfiff09 marine
Tel. +358
5
6.2.5
Prohibit frequency parameters
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.2.10.1
Prohibit frequency
range 1 low limit
-1,00
320,00
Hz
0,00
509
0=Not used
P2.2.10.2
Prohibit frequency
range 1 high limit
0,00
320,00
Hz
0,00
510
0=Not used
P2.2.10.3
Ramp time factor
0,1
10,0
x
1,0
518
Multiplier of the currently
Selected ramp time
between prohibit
frequency limits.
Table 6-3. Prohibit frequencies (G2.5)
6.2.6
Motor Potentiometer
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.2.11.1
Motor potentiometer
ramp rate
0,10
2000,00
Hz/s
1,00
331
Ramp rate for motor
potentio meter
P2.2.11.2
Motor potentiometer
frequency reference
memory reset
0
2
1
367
0=No reset
1=Reset in stop state
2=Reset in powered down
P2.2.11.3
Motor potentiometer
reference copy
0
2
0
366
0=No copy
1=Copy Reference
2=Copy output frequency
Table 6-4. Motor potentiomer (G2.5)
6.2.7
Adjust Reference
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.2.12.1
Adjust input
0
5
0
493
0=Not used
1=AI1
2=AI2
3=AI3
4=AI4
5=Fieldbus
P2.2.12.1
Adjust minimum
0,0
100,0
%
0,0
494
Adjust limit to decrease
ref.
P2.2.12.1
Adjust maximum
0,0
100,0
%
0,0
495
Adjust limit to increase
ref.