6. MARINE APPLICATION PARAMETER LIST
6.1 Basic parameters
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.1.1
Minimum frequency
0,00
P2.1.2
Hz
0,00
101
P2.1.2
Maximum frequency
P2.1.1
320,00
Hz
50,00
102
NOTE: If f
max
> than the
motor synchronous speed,
check suitability for motor
and drive system
P2.1.3
Motor nominal
voltage
180
690
V
NX2: 230V
NX5: 400V
NX6: 690V
110
Check the rating plate of
the motor. Note also used
connection Delta/Star
P2.1.4
Motor nominal
frequency
8,00
320,00
Hz
50,00
111
Check the rating plate of
the motor
P2.1.5
Motor nominal
speed
24
20 000
rpm
1440
112
The default applies for a 4-
pole motor and a nominal
size frequency converter.
P2.1.6
Motor nominal
current
0,1 x I
H
2 x I
H
A
I
H
113
Check the rating plate of
the motor.
P2.1.7
Motor cos
0,30
1,00
0,85
120
Check the rating plate of
the motor
P2.1.8
Motor Nominal
Power
0,0
3200,0
kW
0,0
116
Check the rating plate of
the motor
P2.1.9
Magnetizing current
0,00
100,00
A
0,00
612
0,00 A = Drive uses
estimated value from
motor name plate values
P2.1.10
Identification
0
4
0
631
0=No action
1=Identification w/o run
2=Identification with run
3=Encoder ID Run
4=Ident All
5=Absolute encoder,
locked rotor
NOTE: Set motor control
mode to Freq Control
before identification!
P2.1.11
Motor type
0
1
0
650
0=Induction Motor
1=PMS Motor
Table 6-1. Basic parameters G2.1