V1.25.3 FB Torque Reference % ID 1140
Torque reference value from fieldbus
Default Control of FB PD 1
V1.25.4 FB Limit Scaling % ID 46
Limit scaling input value from fieldbus.
Default Control of FB PD 2.
V1.25.5 FB Adjust Reference % ID 47
Reference adjustment value from fieldbus.
Default Control of FB PD 3.
V1.25.6 FB Analog Output % ID 48
Fieldbus value to control analogue output.
Default Control of FB PD 4.
V1.25.7 FB Motor Current A ID 45
Motor current (drive independent) given with one decimal point.
V1.25.8 Fault Word 1 ID 1172
Different faults are collected to two words that can be read from fieldbus or with
NCDrive PC software.
Fault Word 1 ID1172
Fault
Comment
b0
Over Current or IGBT
F1, F31, F41
b1
Over Voltage
F2
b2
Under Voltage
F9
b3
Motor Stalled
F15
b4
Earth Fault
F3
b5
Motor Under Load
F17
b6
Drive over temperature
F14
b7
Motor Over Temperature
F16, F56, F29
b8
Input Phase
F10
b9
Brake resistor over temperature
F42
(Not implemented)
b10
Device Changed
F37, F38, F39, F40, F44, F45
(Not implemented)
b11
Keypad or PCControl
F52
b12
FielBus
F53
b13
SystemBus
F59
b14
Slot
F54
b15
4 mA
F50