User`s manual
apfiff09 marine vacon • 243
24-
6
10.3 Combination 3, ByPass Basic
10.3.1
Control Word Combination 3, ByPass Basic
Main Control Word for Profibus in Combination 3
FALSE
TRUE
Comment
b0
STOP
START
b1
Clockwise
Counter clockwise
b2
No action
FAULT RESET (0 -> 1)
b3
FB DIN1
FB DIN1
b4
FB DIN2
FB DIN2
b5
FB DIN3
FB DIN3
b6
FB DIN4
FB DIN4
b7
FB DIN5
FB DIN5
b8
Not used
Not used
b9
Not used
Not used
b10
Not used
Not used
b11
Not used
Not used
b12
Not used
Not used
b13
Not used
Not used
b14
Not used
Not used
b15
Not used
Not used
10.3.2
Status Word Combination 3, ByPass Basic
selected what is the status word, default is Combination 2 Status Word, ProfiDrive type ID68 V1.3.2
MainStatusWord. Below Status Word can be selected with P2.10.17 GSW Data by setting it to ID64
Main Status Word for Profibus in Combination 3
FALSE
TRUE
Comment
b0
Not Ready
READY
b1
STOP
RUN
b2
Clockwise
Counter clockwise
b3
NO FAULT
FAULT ACTIVE
b4
No Warning
Warning
b5
Reference ≠ Actual
value
Reference = Actual
value
b6
Speed > Zero
At Zero Speed
b7
Flux Not Ready
Flux Ready
b8
TC Speed Limit Active
TC Speed Limit Not
Active
b9
Detected Encoder
Direction Clockwise
Encoder Direction
Counter clockwise
b10
UV Fast Stop Active
UV Fast Stop Not
Active
b11
Not used
Not used
b12
Not used
Not used
b13
Not used
Not used
b14
Not used
Not used
b15
Not used
Not used
SM = Profibus board State Machine